Releases vs Ex hazardous area classification

Grades of release (or types of source)

Three grades of release 3 are defined in terms of their likely frequency and duration.

Continuous grade release

A release which is continuous or expected to occur for long periods: the cumulative duration of release exceeds 1000 hours per year.

Example: Gaseous atmosphere in a hydrocarbon storage tank.

Primary grade release

A release which can be expected to occur periodically or occasionally during normal operation:

the cumulative duration of release is in the range of 10 to 1000 hours per year.

Examples: Sampling connection (for regular, open to atmosphere sampling), operating purge, drain.

Secondary grade release

A release which is not expected to occur in normal operation and, if it does, is likely to do so only infrequently and for short periods: the cumulative duration of release is less than 10 hours per year 4.

Examples: Flanges, pump seals.

All need to be identified and tracked if not room based you proceed. You shall always choose but then follow your methodology. Mixing possible, but not recommended.